Prismatic Central Boilers are compatible with usage of wood or coke type of solid fuels. Whenever required, they can be turned out to liquid or gas fuel using systems. Produced with 11 capacity ranges with high performance. Central Boilers provides economical heating and are user friendly as well.
Technology Manufactured with TS EN 303-5 and TS497 standards as long lasting products. Reaches to set temperature promptly with special 3 pass design and by the turbulators holding the gas in the smoke tubes forming out a heat recovery system. Thus, the fuel compsumption is reduced at the lowest level.
Elegantly Designed Control Panel All the functions of the boiler can be controlled easily by the control panel. Overheating and useless fuel consumption are prevented by providing heating control.
Complete combustion is provided by Specially designed fan by upper and lower air circulation. Thus, high efficiency and envorenmental protection is also provided.
Automatic Stop Fan and circulation pump stop automatically once the fuel in the boiler is finished and causes energy conservation.
By Hot water tank add, it is possible to obtain usage water.
Burning Delay Independent from the boiler temperature, in case the ambient temperature is at already desired levels, the system can be shut down at the control panel. In this case the burning fuel will be blacken and the burning will be postponed to next start-up. Once the boiler is turned on again, burning will be continued without any need of ignition. Burning delay is possible up to 24 hours depending on the quality of the coal.
User Friendly By the wide fuel feeding and ash doors, fuel feeding, flaming, ash removing can be done easily.
Multifuel usage Allthough the boilers are designed for solid fuel, they can be easily converted to the liquid and gas fuel using systems by a simple modification.
Casing Outer sheets are painted by electrostatic powder paint against corrosion which also provides an elegant appearance of boiler.
Automatic Stop Fan and circulation pump stop automatically once the fuel in the boiler is finished and causes energy conservation.

MODEL-SERIES | PBP | 130 | 160 | 180 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 600 | |
Fuel Type | Wood - Coal - Biomass | ||||||||||||
Heat Output | kW | 151 | 186 | 209 | 233 | 291 | 349 | 407 | 465 | 523 | 582 | 698 | |
kcal/h | 130.000 | 160.000 | 180.000 | 200.000 | 250.000 | 300.000 | 350.000 | 400.000 | 450.000 | 500.000 | 600.000 | ||
Burning Chamber Height | mm | 510 | 560 | ||||||||||
Burning Chamber Width | mm | 600 | 700 | 800 | 755 | 790 | |||||||
Burning Chamber Lenght | mm | 1020 | 1220 | 1320 | 1045 | 1400 | 1510 | ||||||
Burning Chamber Volume | dm3 | 312 | 373 | 436 | 471 | 539 | 402 | 462 | 619 | 668 | |||
Fuel Entry | mm | 440x340 | 460x380 | ||||||||||
Water Volume | lt | 320 | 400 | 480 | 560 | 640 | 890 | 925 | 1240 | 1195 | 1505 | 1570 | |
Boiler Weight | kg | 70 | 855 | 985 | 1050 | 1205 | 1595 | 1745 | 1960 | 2015 | 2305 | 2560 | |
Required Draft | mbar | 0,42-0,45 | 0,44-0,47 | 0,45-0,49 | 0,47-0,51 | 0,50-0,53 | |||||||
Min-Max Operating Temperature | ºC | 45-85 | |||||||||||
Water Return Temperature (Recommended) | ºC | 35 | |||||||||||
Maximum Operating Pressure | bar | 3 | |||||||||||
Test Pressure | bar | 5 | |||||||||||
Dimensions | Width (a) | mm | 760 | 860 | 960 | 1130 | 1180 | 1390 | |||||
Lenght (b) | mm | 1615 | 1815 | 1915 | 2280 | 2400 | 2750 | ||||||
Chimney Connection Height © | mm | 1370 | 1465 | 1600 | 1665 | 1675 | |||||||
Boiler Total Height (h) | mm | 1640 | 2000 | 2055 | 2095 | 2125 | |||||||
Exhaust Gas Connection Diameter (Chimney) | mm | 220 | 300 | 350 | |||||||||
Min-Max Flue Temperature | ºC | 170-210 | |||||||||||
Boiler Outlet-Inlet | R" | 2" | 2 ½" | DN80 | DN100 | DN125 | |||||||
Expansion Tank Outlet-Inlet | R" | 1 ½" | 2" | ||||||||||
Filling - Discharge | R" | 1/2" | 3/4" | ||||||||||
Electrical Connection | V/Hz | 230 V-50Hz |